2.4 Distance protection Z<
VM259.EN007
VAMP 24h support phone +358 (0)20 753 3264
61
Fault L1-G inside zone Z1e<
Fault is noticed since one of the voltages in the network area is
dropped below the set ―Phase under-voltage limit‖ limit and
two other voltages are increasing above the set ―Phase over-
voltage limit‖ limit. This phase has to last least 100ms.
When second fault appears another voltage has to drop at least
10% below the healthy phase‖. Also set amount of zero
sequence voltage has to be exceeded (same applies to residual
current if triggering condition U0_I0 is selected).
Selected relay sees the fault 1 (L1-G) inside the zone Z1e<. If
phase priority is selected as ―1-> 2-> 3‖ this relay would trip
and the same would do to the relay opposite the protected line.