Technical description
2 Protection functions
2.13 Thermal overload protection T>
(49)
VM259.EN007
VAMP 24h support phone +358 (0)20 753 3264
101
Initial temperature rise after restart
When the device is switched on, an initial temperature rise of
70 % is used. Depending of the actual current, the calculated
temperature rise then starts to approach the final value.
Alarm function
The thermal overload stage is provided with a separately
settable alarm function. When the alarm limit is reached the
stage activates its start signal.
Figure 2.13-2. Example of the thermal model behaviour.