5.2 Digital inputs
5 Control functions
Technical description
204
VAMP 24h support phone +358 (0)20 753 3264
VM259.EN007
Summary of digital inputs:
DI
Terminal
Operating voltage
Availability
X3:1
48VDC supply for DI1…6
Always
available
1
X3:2
Internal 48VDC
2
X3:3
3
X3:4
4
X3:5
5
X3:6
6
X3:7
7
X7:1
External 18…265 VDC
50…250 VAC
8
X7:2
9
X7:3
10
X7:4
11
X7:5
12
X7:6
X7:7
Common for DI7…12
13
X7:8
External 18…265 VDC
50…250 VAC
14
X7:9
15
X7:10
16
X7:11
17
X7:12
18
X7:13
X7:14
Common for DI13…17
19
X6:1…2
External 18…265 VDC
50…250 VAC
ARC card with 2 DIs
20
X6:3…4
21
X8:1
External 18…265 VDC
50…250 VAC
Additional I/O (X8)
22
X8:2
X8:3
Common for D21…22
23
X8:4
External 18…265 VDC
50…250 VAC
24
X8:5
X8:6
Common for D23…24
25
X8:7
External 18…265 VDC
50…250 VAC
26
X8:8
X8:9
Common for D25…26
27
X8:10
External 18…265 VDC
50…250 VAC
28
X8:11
X8:12
Common for D27…28
29
X8:19...20
External 18…265 VDC
50…250 VAC
If T5 not in
use
30
X8:17...18
If T6 not in
use
31
X8:15...16
If T7 not in
use
32
X8:13...14
If T8 not in
use