Technical description
3 Supporting functions
3.9 Energy pulse outputs
VM259.EN007
VAMP 24h support phone +358 (0)20 753 3264
165
3.9.
Energy pulse outputs
The device can be configured to send a pulse whenever certain
amount of energy has been imported or exported. The principle
is presented in Figure 3.9-1. Each time the energy level reaches
the pulse size, an output relay is activated and it will stay
active as long as defined by a pulse duration setting.
Figure 3.9-1. Principle of energy pulses
The device has four energy pulse outputs. The output channels
are:
Active exported energy
Reactive exported energy
Active imported energy
Reactive imported energy
Each channel can be connected to any combination of the
output relays using output matrix. The parameters for the
energy pulses can be found in the E menu under the submenus
E-PULSE SIZES and E-PULSE DURATION.
Energy pulse output parameters
Parameter Value
Unit
Description
E-PULSE
SIZES
E+
10 … 10 000 kWh
Pulse size of active
exported energy
Eq+
10 … 10 000 kvarh Pulse size of reactive
exported energy
E-
10 … 10 000 kWh
Pulse size of active
imported energy
Eq-
10 … 10 000 kvarh Pulse size of reactive
imported energy
E-PULSE
DURATION
E+
100 … 5000
ms
Pulse length of active
exported energy
Eq+
100 … 5000
ms
Pulse length of
reactive exported
energy
E-
100 … 5000
ms
Pulse length of active
imported energy
Eq-
100 … 5000
ms
Pulse length of
reactive imported
energy