Operation and configuration
2 Local panel user interface
2.4 Configuration and parameter
setting
VM259.EN007
VAMP 24h support phone +358 (0)20 753 3264
33
2.4.5.
Configuring digital outputs DO
The following functions can be read and set via the submenus
of the digital outputs menu:
The status of the output relays (RELAY OUTPUTS 1, 2, 3
and 4)
The forcing of the output relays (RELAY OUTPUTS 1, 2, 3
and 4) (only if Force = ON):
o
Forced control (0 or 1) of the Trip relays
o
Forced control (0 or 1) of the Alarm relays
o
Forced control (0 or 1) of the IF relay
The configuration of the output signals to the output relays.
The configuration of the operation indicators (LED) Alarm
and Trip and application specific alarm leds A, B and C
(that is, the output relay matrix).
NOTE! The amount of Trip and Alarm relays depends on the relay type and
optional hardware.
2.4.6.
Protection menu Prot
The following functions can be read and set via the submenus
of the Prot menu:
Reset all the counters (PROTECTION SET/ClAll)
Read the status of all the protection functions (PROTECT
STATUS 1-x)
Enable and disable protection functions (ENABLED
STAGES 1-x)
Define the interlockings using block matrix (only with
VAMPSET).
Each stage of the protection functions can be disabled or
enabled individually in the Prot menu. When a stage is
enabled, it will be in operation immediately without a need to
reset the relay.
The relay includes several protection functions. However, the
processor capacity limits the number of protection functions
that can be active at the same time.