Modbus TCP / Modbus UDP
vacon • 81
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7
7.3.2.5.3.
FB P
ROCESS
DATA
OUT
Values in these indexes can be only read, not written.
Table 33. Fieldbus Process Data OUT
* Available in future release
Address
Name
Range/Type
16-bit
32-bit*
2101
2151 = High data 2152
= Low data
FB Status Word
Binary coded
2102
-
In case of 16-bit,
FB General Status Word
(High data)
Binary coded
2103
2153 = High data
2154 = Low data
FB Actual Speed
0…10000 (100.00%)
2104
2155 = High data
2156 = Low data
FB Process Data Out 1
2105
2157 = High data
2158 = Low data
FB Process Data Out 2
2106
159 = High data
2160 = Low data
FB Process Data Out 3
2107
2161 = High data
2162 = Low data
FB Process Data Out 4
2108
2163 = High data
2164 = Low data
FB Process Data Out 5
2109
2165 = High data
2166 = Low data
FB Process Data Out 6
2110
2167 = High data
2168 = Low data
FB Process Data Out 7
2111
2169 = High data
2170 = Low data
FB Process Data Out 8
2112*
2171 = High data
2172 = Low data
FB Process Data Out 9
2113*
2173 = High data
2174 = Low data
FB Process Data Out 10
2114*
2175 = High data
2176 = Low data
FB Process Data Out 11
2115*
2177 = High data
2178 = Low data
FB Process Data Out 12
2116*
2179 = High data
2180 = Low data
FB Process Data Out 13
2117*
2181 = High data
2182 = Low data
FB Process Data Out 14
2118*
2183 = High data
2184 = Low data
FB Process Data Out 15
2119*
2185 = High data
2186 = Low data
FB Process Data Out 16