The information in an EDS allows configuration tools to provide informative screens that guide a
user through the steps necessary to configure a device. An EDS provides all of the information nec-
essary to access and alter the configurable parameters of a device.
The option boards have multiple EDS files, at least one per AC drive type. You can download the AC
drive specific EDS from Danfoss website (
http://drives.danfoss.com
). Also, see Chapter 6.1.9 "EIP
EDS files are split into two formats: static and dynamic. Only difference between these types is that
the static versions list all assembly pairs and all Listen Only and Input Only connections. PLC appli-
cation development tools usually show this as a list where you can simply select the wanted pair.
But if you want to mix assembly pairs, for example to command the drive with assembly 21 and get
assembly 117 back, you can use the dynamic-version. It allows you to input manually used assembly
instances and their sizes.
9.1.4
LED functionality
The option boards’ LEDs follow the CIP standard when the EtherNet/IP is set as the active protocol.
The LEDs on the option board are not labeled as the CIP defines. The LED labels are described in
the following table.
9.1.4.1
Module Status LED
The Module status LED is labeled on the board as "BS". It shows the status of the module, that is, if
a fault has occurred or if the module has been configured. The MS LED functionality is described in
the following table.
Table 104. OPTE9 EtherNet/IP LED Definitions
LED label
Description
CIP
definition
RN
Network Status Indicator
NS
ER
IO connection indicator
-
BS
Module Status indicator
MS
Table 105. EtherNet/IP Module Status LED functionality
LEDs
State
Summary
Requirement
Steady Off
No power
If no power is supplied to the device, the
module status indicator is steady off.
Steady Green
Device opera-
tional
If the device is operating correctly, the mod-
ule status indicator is steady green.
Flashing Green
Standby
If the device has not been configured, the
module status indicator is flashing green.
Flashing Red
Minor fault
If the device has detected a recoverable
minor fault, the module status indicator is
flashing red.