vacon • 128
PROFINET IO
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
8.4.8.4
Changing the value of drive parameter ID 103 (successful)
The following information is used for this request:
Following table contains messages sent during writing value to ID 103.
Answer indicates a successful operation.
Table 94. Request to write the value of parameter ID 103
Field
Contents
Request reference
0x04
Request ID
0x02 = Write parameter
Axis Number
0x01
No. of Parameters
0x01
Attribute
0x10 = Value
No. of elements
0x01
Parameter Number
0x2711 (10001d)
Subindex
0x0067 (103d)
Parameter datatype
0x42 = WORD
Number of parameters
0x01
Value: HI byte
0x00
Value: LOW byte
0x28
Table 95. Messages sent and received during writing value to ID 103
Message
Operation
Data
1
Write request
Request header
0x04 0x02 0x01 0x01
Parameter address
0x10 0x01 0x27 0x11 0x00 0x67
Parameter value
0x42 0x01 0x00 0x28
2
Write request response from AC drive to PLC
-
PLC waits until AC drive has finished processing the requested operation
3
PLC sends read request
4
Read request
response
Response header
0x04 0x02 0x01 0x01