6
vacon • 64
Commissioning
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
6.1.7
Profinet IO - Name of Station
The Profinet IO "Name of Station" parameter can be set via VACON
®
Live or NCIPConfig. Other
possibility is to set this name by writing it over Ethernet with the DCP protocol. The name is empty
if no name is set, or if the name has been set as "temporary" by network device with DCP protocol.
Maximum length for this parameter is 240 characters.
Because VACON
®
NX, VACON
®
20, VACON
®
20 X and VACON
®
20 CP drives do not support
parameters with string datatype, a parameter with integer value (NOS Device ID) can be used
instead. When a non-zero value is set, the option board generates the Name Of Station value using
application id and this new parameter. This integer value can then be backed up and restored when
needed. This way the AC drive can be replaced and it will retain the same Name Of Station value
after parameters are restored.
If NOS Device ID parameter is used, the option board always generates the Name Of Station value
during drive startup. The used value can be overwritten by PLC or PC tools, but the written value is
active only until the AC drive is restarted again.
For example if Multi-purpose application is used and NOS Device ID is set to '7', the Name Of Station
will be "apfiff06-7". Note that when using "NOS Device ID" if drive application changes, generated
Name Of Station value also changes.
We recommend you to use LLDP capable devices and the topology feature in (for example) Siemens
TIA Portal. This way, the PLC always sets the Name Of Station and IP settings based on devices
location in Ethernet network. This way there is no need to set manually Name Of Station or use "NOS
Device ID" parameter.
The Name Of Station value is shown in monitoring view (except for of VACON
®
20, VACON
®
20 X and
VACON
®
20 CP). Displayed value is limited to 12 characters in VACON
®
NX and to 18 characters in
VACON
®
100 family.
For example "auxpump22tower4" is shown as "..mp22tower4" in VACON
®
NX.
6.1.8
EIP Input and Output instance
These parameters will show what instances are being used now. The instances actually used are
taken from the IO connection open request. So, although these values are parameters they act more
like monitoring values. Input and output parameters were removed in newer firmware version and
replaced with monitoring values. The monitoring values show currently used instance numbers.
6.1.9
EIP Product code offset
This value can be used to differentiate drives for the PLC program. For example, if one drive is
running a different application (with different parameters) than other drives, this offset in the
product code will enable the PLC to use a different EDS file to read those parameters from this drive.
Remember that if you change this value, you need also to change the EDS file used or change the
product code value in your EDS file.
6.1.10
Mode
For OPTEA the "Mode" parameter has different content when installed to VACON
®
100 or to NX
family drive. When installed to NX family drive and "OPTCx" mode is selected, OPTEA will emulate
behavior of old C-series Ethernet option boards as accurately as possible.