PROFINET IO
vacon • 105
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
8
Table 66. Overview of the assignments of bits of the control word 1
*Bits in a control word do not have any effect unless bit 10 is enabled.
Bit 0: Switching ON / OFF
This bit is used in combination with other bits to enable operation of the drive. When this bit is set
to 0 during operation, the drive performs a ramp stop.
Bit 1: Coast stop command
This bit is used to request a coast stop to be executed. When it is set to 0 during operation, the drive
performs a coast stop.
Bit 2: Quick stop command
This bit is used to request a quick stop to be executed. When it is set to 0 during operation, the drive
quickly ramps down to zero speed and stops.
Bit 3: Enabling of operation
This bit is used in combination with other bits to enable operation of the drive. When it is set to 0
during operation, the drive performs a coast stop.
Bit 4: Enabling of ramp generator
This bit is used in combination with other bits to enable operation of the drive. When it is set to 0
during operation, the drive quickly decelerates to zero speed.
Bit 5: Freezing of ramp generator
This bit can be used to freeze the setpoint value used by the drive. The value is frozen if this bit is
set to 0. If the bit is 1, the setpoint value provided by the master is continuously updated.
Bit 6: Enabling of setpoint value
This bit can be used to disable the fieldbus setpoint value. If this bit is set to 0, the option board
ignores the setpoint value by the master and instead uses a setpoint value of 0. During operation, if
this bit is set to 0, the drive decelerates to a standstill.
Bit
Significance
Bit value is 1
Bit value is 0
0
ON
OFF
1
No Coast Stop (no OFF2 )
Coast Stop (OFF2)
2
No Quick Stop (no OFF3)
Quick Stop (OFF3)
3
Enable Operation
Disable Operation
4
Enable Ramp Generator
Reset Ramp Generator
5
Unfreeze Ramp Generator
Freeze Ramp Generator
6
Enable Setpoint
Disable Set Point
7
Fault Acknowledge (0 -> 1)
8
Not used
9
Not used
10*
Control by PLC
No control by PLC
11
Device-specific
Device-specific
12-15
Device-specific
Device-specific