EtherNet/IP
vacon • 183
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
9
Control and Status Word monitoring values
When using this telegram, monitoring values contains values as shown in the following table. Status
word values depend on used input instance.
9.3.1.2
CIP Input instances
9.3.1.2.1.
A
SSEMBLY
I
NSTANCE
70 – B
ASIC
S
PEED
C
ONTROL
I
NPUT
Control and Status Word monitoring values
When using this telegram, monitoring values contains values as shown in the following table.
Control word values depend on used output instance.
Table 166.
Instance
Octet
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
23
(length 6)
0
Net-
proc
NetRef NetCtrl
Fault
Reset
Run
Rev
Run
Fwd
1
Drive Mode
2
Speed Reference (Low Octet)
3
Speed Reference (High Octet)
4
Process Reference (Low Octet)
5
Process Reference (High Octet)
Table 167. Control and Status Word monitoring values
Name
Value
Drive CW
FBFixedControlWord
Protocol CW
CIP Control Word
Table 168.
Instance
Octet
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
70
(length 4)
0
Runnin
g1
Faulted
1
2
Speed Actual (Low Octet)
3
Speed Actual (High Octet)
Table 169. Control and Status Word monitoring values
Name
Value
Drive SW
FBFixedStatusWord
Protocol SW
FBGeneralStatusWord