APPENDIX 4 - FIELDBUS PARAMETRISATION
vacon • 243
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
14
14.2
Controlling Fieldbus Parameter
VACON
®
100 family drives have “Controlling Fieldbus” parameter. It is used select the "Controlling
Fieldbus" parameter to select the instance from which the process data is sent to the drive
application. By default the setting is in "Automatic" and the functionality (when receiving process
data from multiple sources) is application dependent.
For example, if the option board has been installed to slot E and it is used with PROFINET to control
the drive, user can select "Slot E" as value for this parameter. Now only the process data from the
option board in slot E is forwarded to the application. All other fieldbusses will still receive process
data out. With this setting it is possible to prevent that the monitoring fieldbusses accidentally write
process data in.
Rem. Control place 1
freq. ref. sel.
117
3 = Fieldbus
7
P 3.3
Table 223. Parametrization for VACON
®
20X (standard application)
Parameter name
ID
Value
Default
Panel Tree
Motor control mode
600
0 = Frequency
1 = Speed
0
P 8.1
Control place selection
125
2 = Fieldbus
0
P 1.11
Local / remote
211
0 = Remote
0
P 3.2.2
Frequency ref. sel.
1819
5 = Fieldbus
5-7
P 1.12
Table 224. Parametrization for VACON
®
NXP (multipurpose application)
Parameter name
ID
Value
Default
Panel Tree
Motor control mode
600
0 = Frequency
1 = Speed
2 = Torque
0
P 2.6.1
Control place selection
125
3 = Fieldbus
1
P 3.1
Fieldbus Ctrl Ref.
122
9 = Fieldbus
3
P 2.1.13
Table 225.
Value name
Value
Description
Automatic
1
Process data from all sources is forwarwed to application
Slot D
2
Only process data from slot D is forward to application.
Value is visible only, if option board is installed to slot D.
Slot E
3
Only process data from slot E is forward to application.
Value is visible only, if option board is installed to slot E.
RS485
4
Only process data from VACON
®
100 family internal RS 485
protocol is forwared to application
Parameter name
ID
Value
Default
Panel Tree