APPENDIX 1 - VACON® IO DATA DESCRIPTION
vacon • 205
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
11
11.
APPENDIX 1 - VACON
®
IO DATA DESCRIPTION
11.1
VACON
®
Control Word - FBFixedControlWord
The VACON
®
Control Word is composed of 32 bits. This control data is split into two words:
FBFixedControlWord consist of the first 16 bits and FBGeneralControlWord consist of the remaining
16 bits.
While functionality of the FBFixedControlWord is fixed in VACON
®
standard applications,
functionality of the FBGeneralControlWord is totally application specific and can vary even in
VACON
®
standard applications.
FBFixedControlWord bit definitions are described in the table below. Note that there are some
control word bit modifications in VACON
®
NXP AC drive. These modifications are described in
Table 207. Unused bits have to be set to zero.
Table 206. FBFixedControlWord bits
Bit
Function
Description
0
Start/Stop
0
Stop request from fieldbus.
1
Run request from fieldbus.
1
Direction
0
Requested direction is "FORWARD".
1
Requested direction is "REVERSE".
2
Fault reset
0
No action.
1
No action when 1->1. Rising edge (0->1) = Active
faults, alarms and infos are reset.
3
Stop mode 1
0
Stop mode is unmodified.
1
Stop mode is overridden to "Coasting".
4
Stop mode 2
0
Stop mode is unmodified.
1
Stop mode is overridden to "Ramping".
5
Quick ramp time
0
Normal deceleration ramp time.
1
Deceleration ramp time is switched to shorter
than normal.
6
Freeze Setpoint
0
Changes in the setpoint value from fieldbus
(FBSpeedReference) are taken into use by the
application.
1
Changes in the setpoint value from fieldbus
(FBSpeedReference) are not taken into use by the
application.
7
Setpoint to Zero
0
The setpoint value from fieldbus is taken from FB
Speed Reference.
1
The setpoint value from fieldbus is changed to 0.
8
Request Fieldbus
Control
0
Control Place is as parameterized in the drive
(unchanged).
1
Control Place is overridden to Fieldbus Control.
9
Request Fieldbus
Reference
0
Source of the setpoint value is as parameterized
in the drive (unchanged).
1
Source of the setpoint value is overridden to
Fieldbus.