APPENDIX 1 - VACON® IO DATA DESCRIPTION
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1) This functionality can be enabled/disabled by application from drive parameters.
Table 207. FBFixedControlWord modifications in VACON
®
NXP
10
Jogging 1
0
No action.
1
Jogging request with jogging reference 1.
11
Jogging 2
0
No action.
1
Jogging request with jogging reference 2.
12
Quick stop
0
No action.
1
Drive executes quick stop / emergency stop.
13
Reserved
0
-
1
-
14
Reserved
0
-
1
-
15
Master connected
1)
0
Only in NXP. Fieldbus sets this bit to zero when it
detects that there is no connection to master.
1
Only in NXP. Fieldbus sets this bit to one when it
detects valid connection from the master.
Bit
Function
Description
3
Fieldbus DIN1
0
Fieldbus DIN 1 off
1
Fieldbus DIN 1 on
4
Fieldbus DIN2
0
Fieldbus DIN 2 off
1
Fieldbus DIN 2 on
5
Fieldbus DIN3
0
Fieldbus DIN 3 off
1
Fieldbus DIN 3 on
6
Fieldbus DIN4
0
Fieldbus DIN 4 off
1
Fieldbus DIN 4 on
7
Fieldbus DIN5
0
Fieldbus DIN 5 off
1
Fieldbus DIN 5 on
Bit
Function
Description