vacon • 45
Parameter description
3
P6.5
RO1
SIGNAL
SELECTION
P6.6
RO2
SIGNAL
SELECTION
Function for internal relays.
0: not used
1: Ready
2: Run
3: Fault
4: Fault inverted
5: Fault or warning
6: Reverse
7: At speed (motor control feedback)
8: Output freq superv
9: Output current superv
10: ASi Output 1
11: ASi Output 2
12: ASi Output 3
13: ASi Output 4
Note: relay terminals are not accessible in standard V20X+D drive.
P6.7
RO1 ON
DELAY
P6.8
RO1 OFF
DELAY
Possible delays for ON/OFF transitions.
P6.9
RO1
INVERSION
Inversion of relay state.
P6.10
RO2 ON
DELAY
P6.11
RO2 OFF
DELAY
Possible delays for ON/OFF transitions.