Parameter description
vacon • 52
Service support: find your nearest Vacon service center at www.vacon.com
3
3.10
Protections
P10.1 E
ARTH
FAULT
0: No action
1: Warning
2: Fault
Output currents sum not zero.
P10.2 M
OTOR
S
TALL
FAULT
0: No action
1: Warning
2: Fault
This is an overload protection. Stall is recognized by maximum motor current (=P1.5) and low
output frequency.
Figure 8. Stall characteristic settings.
P10.3 S
TALL
TIME
LIMIT
This time can be set between 0.0 and 300.0 s.
This is the maximum time allowed for all stage. the stall time is counted by an internal up/down
counter. If the stall time counter value goes above this limit the protection will cause a trip.
f
I
Par. P1.6
Par. P10.4
Stall area