Description of Groups
vacon • 24
Service support: find your nearest Vacon service center at www.vacon.com
2
2.2.9
Group Motor Control: Menu PAR G9
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P9.1
Field Weakening
Point frequency
8.00
320.00
Hz
50.00
602
Advanced
Field weakening point fre-
quency
P9.2
Field Weakening
Point voltage
10.00
200.00
%
100.00
603
Advanced
Voltage at FWP as % of
Motor nominal voltage
P9.3
U/f ratio selection(*)
0
2
0
108
Advanced
0 = linear
1 = quadratic
2 = programmable
P9.4
U/f midpoint
frequency(*)
0.00
P9.2
Hz
50.00
604
Advanced
Midpoint frequency for pro-
grammable U/f curve
P9.5
U/f midpoint volt-
age(*)
0.00
P9.3
%
100.00
605
Advanced
Midpoint voltage for pro-
grammable U/f curve
P9.6
Zero frequency
voltage(*)
0.00
40.00
%
0.00
606
Advanced
Voltage at 0,00 Hz as % of
Motor nominal voltage
P9.7
RS voltage drop(*)
0.00
100.00
%
0.00
662
Advanced
Voltage drop on the motor
windings as % of Motor
nominal voltage
P9.8
Switching frequency
1.5
16.0
kHz
4.0
601
Advanced
Increasing the switching
frequency reduces the
capacity of the drive.
P9.9
Drooping Mode
0
1
1
1813
Advanced
0: constant
1: speed dependent
P9.10
Droop filter time
0.00
3.00
s
0.10
1814
Advanced
Constant time of filter on
droop calculation
P9.11
Brake chopper
0
2
0
504
Advanced
0 = Disabled
1 = Enabled in RUN
2 = Enabled in READY
P9.12
Brake chopper level
600
900
V
650
1807
Advanced
DC-link voltage to start
chopper.
P9.13
DC brake current
0.3 x I
H
2 x I
H
A
I
H
507
Basic
Defines the current injected
into the motor during DC-
braking. 0 = Disabled
P9.14
DC braking time at
stop
0.00
600.00
s
0.00
508
Basic
Determines if braking is ON
or OFF and the braking time
of the DC-brake when the
motor is stopping.
P9.15
Frequency to stop DC
braking at ramp stop
0.10
10.00
Hz
1.50
515
Basic
The output frequency at
which the DC-braking is
applied.
P9.16
DC braking time at
start
0.00
600.00
s
0.00
516
Basic
Determines the braking
time of the DC-brake when
the motor is starting.
P9.17
Overvoltage
controller
0
1
0
1853
Service
0 = Enabled
1 = Disabled
P9.18
Undervoltage
controller
0
1
0
1854
Service
0 = Enabled
1 = Disabled
P9.19
Switching frequency
controller
0
1
0
1855
Service
0 = Enabled
1 = Disabled
Table 38: Group Motor control.
NOTE!
(*) Parameter is automatically set by motor identification.