vacon • 23
Description of Groups
2
2.2.8
Group Supervisions: Menu PAR G8
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P8.1
Running Ok speed
tolerance
0.0
100.0
%
90.0
1880
Advanced
P8.2
Output frequency
supervision
0
2
2
315
Advanced
0 = not used
1 = Low limit
2 = High limit
P8.3
Frequency supervision
limit
0.00
P3.2
Hz
35.00
316
Advanced
Output frequency super-
vision threshold
P8.4
Current supervision
limit
0.00
2 x I
H
A
0.00
1811
Advanced
Current supervision
threshold
P8.5
Process display source
selection
0
4
1
1036
Advanced
Selection of variable pro-
portional to process:
0 = Output frequency
1 = Motor speed
2 = Motor torque
3 = Motor power
4 = Motor current
P8.6
Process display
decimal digits
0
3
1
1035
Advanced Decimals on display
P8.7
Process display max
value
0.0
3276.7
100.0
1034
Advanced
Process display max
value (it depends on
P7.11: with zero decimal
digit the max value is
32767; with 1 decimal
digit the max value is
3276.7)