vacon • 61
Parameter description
3
3.12.1.2
Fieldbus Data OUT: Slave ->Master
Notes:
•
Fieldbus different from Modbus have their own Status Word (see manual of the specific
fieldbus board).
Modbus
register
Name
Description
Range
2101
Status word
Drive state
Binary coded:
b0: Ready
b1: Run
b2: Reverse
b3: Fault
b4: Warning
b5: Freq. reference reached
b6: Zero speed
2102
General Status word
Drive state
b0: Ready
b1: Run
b2: Reverse
b3: Fault
b4: Warning
b5: Freq. reference reached
b6: AUTO mode
b7: MANUAL mode
b8: Brake command
2103
Actual speed(*)
Actual speed
0...10000 as 0,00...100,00%
of Min freq. - Max freq.
range
2104
Fieldbus Data OUT 1
Programmable
See P12.1
2105
Fieldbus Data OUT 2
Programmable
See P12.2
2106
Fieldbus Data OUT 3
Programmable
See P12.3
2107
Fieldbus Data OUT 4
Programmable
See P12.4
2108
Fieldbus Data OUT 5
Programmable
See P12.5
2109
Fieldbus Data OUT 6
Programmable
See P12.6
2110
Fieldbus Data OUT 7
Programmable
See P12.7
2111
Fieldbus Data OUT 8
Programmable
See P12.8
Table 47. Modbus data outputs. They can vary depending on fieldbus used (See specific
fieldbus option board installation manual).