vacon • 19
Description of Groups
2
2.2.4
Group Ramps: Menu PAR G4
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P4.1
Acceleration time 1
0.1
3000.0
s
3.0
103
Basic
Defines the time required
for the output frequency to
increase from zero fre-
quency to maximum fre-
quency
P4.2
Deceleration time 1
0.1
3000.0
s
3.0
104
Basic
Defines the time required
for the output frequency to
decrease from maximum
frequency to zero fre-
quency
P4.3
Ramp 1 shape
0.0
10.0
s
0.0
500
Basic
Rounded speed profile.
P4.4
Acceleration time 2
0.1
3000.0
s
10.0
502
Advanced
Time from 0 to max fre-
quency
P4.5
Deceleration time 2
0.1
3000.0
s
10.0
503
Advanced
Time from 0 to max fre-
quency
P4.6
Ramp 2 shape
0.0
10.0
s
0.0
501
Advanced Rounded speed profile.
P4.7
Acceleration time 2
freq. threshold
0.00
P3.2
Hz
0.00
527
Advanced
Threshold for auto change
from acc1 to acc2
P4.8
Deceleration time 2
freq. threshold
0.00
P3.2
Hz
0.00
528
Advanced
Threshold for auto change
from dec2 to dec1
P4.9
Quick Stop dec.
time
0.1
3000.0
s
1.0
1889
Basic
Time from max frequency
to 0
Table 33: Group Ramps.