Description of the terminals (D-option with Profibus)
The following pictures describe the power and M12 terminals in Vacon 20X drives with D-option
and Profibus connection.
1.4.1
MU2 connections
Figure 3. Power and control terminals in MU2.
Mains supply / Type HAN Q5/0 (Male)
Pin
Function
1
L1
2
L2
3
L3
4
-
5
-
PE
Protective Earth
Table 11. Mains supply connector, MU2.
Motor output / Type HAN Q8 (Female)
Pin
Function
1
U
2
Not connected
3
W
4
Brake (-)
5
Temperature sensor (+)
6
Brake (+)
7
V
8
Temperature sensor (-)
PE
Protective Earth
Table 12. Motor supply connector, MU2
X5
X4
Mains supply
Motor output
X3
X2
X1