Description of Groups
vacon • 16
Service support: find your nearest Vacon service center at www.vacon.com
2
2.2.2
Group Start/Stop Settings: Menu PAR G2
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P2.1
AUTO
Start/Stop logic
0
3
0
300
Basic
Logic = 0:
Start sgn 1 = Start Forward
Start sgn 2 = Start Back-
ward
Logic =1:
Start sgn 1 = Start Forward
(edge)
Start sgn 2 = Start Back-
ward (edge)
Logic = 2:
Start sgn 1 = Start
Start sgn 2 = Reverse
Logic = 3:
Start sgn 1 = Start (edge)
Start sgn 2 = Reverse
P2.2
AUTO
Run control
0
1*
1
125
Advanced
0= Start 1-Start 2 signals
1= non-ASi fieldbus
P2.3
Start function
0
1
0
505
Advanced
0=Ramping
1=Flying start
P2.4
Stop function
0
1
0
506
Advanced
0=Coasting
1=Ramping
P2.5
Quick Stop Function
0
1
0
1896
Basic
0=Signal level
1=Signal edge
P2.6
Manual Start mode
0
1
1
1899
Advanced
0=Signal level
1=Signal edge
Table 31: Group Start/Stop settings.
NOTE!
(*)Selection 1 is available only if ASi board is not installed. In this case a different
fieldbus can be used to control the drive. When ASi board is installed this param-
eter is automatically set to 0.