vacon • 27
Description of Groups
2
2.2.11
Group Automatic reset: Menu PAR G11
P10.12
Motor thermal time
constant
1
200
min
45
707
Advanced
The time constant is
the time within which
the calculated thermal
stage has reached 63%
of its final value.
P10.13
Fieldbus communica-
tion fault
0
2
1
733
Advanced See P10.1
P10.14
Thermistor fault
0
2
0
732
Service
See P10.1
P10.15
Response to Safe
Torque Off
0
3
1
1876
Advanced
0 = No action
1 = Warning
2 = Fault, not stored in
history menu
3 = Fault, stored in his-
tory menu
P10.16
Input phase fault
0
2
2
1877
Service
See P10.1
P10.17
Input phase fault ripple
limit
0
75
0
1893
Service
0 = internal value
1 = max sensitivity ->
75 = min sensitivity
P10.18
Motor temperature
initialization
0
2
2
1891
Service
0 = start from mini-
mum
1 = start from constant
value
2 = start from last
value
P10.19
Motor temperature
initial value
0
100
%
33
1892
Service
Initial value(P10.18 = 1)
or factor for last previ-
ous value(P10.18 = 2)
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P11.1
Automatic reset
0
1
0
731
Basic
0 = Disabled
1 = Enabled
P11.2
Wait time
0.10
10.0
s
0.50
717
Advanced
Wait time before the first
reset is executed.
P11.3
Trial time
0.00
60.0
s
30.00
718
Advanced
When the trial time has
elapsed, and the fault is still
active, the drive will trip to
fault.
P11.4
Number of trials
1
10
3
759
Advanced
NOTE: Total number of trials
(irrespective of fault type)
P11.5
Restart function
0
2
0
719
Advanced
The start mode for Automatic
reset is selected with this
parameter:
0 = Ramp
1 = Flying start
2 = According to par. P2.3
Table 40: Group Automatic reset.
Table 39: Group Protections.