vacon • 29
Description of Groups
2
2.2.13
Group Analogue output: Menu Par G13
2.2.14
Group User interface: Menu Par G14
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P13.1
AO1 function
0
6
2
307
Service
0 = Not used (fixed 100%)
1 = Freq. reference (0-fmax)
2 = Output freq. (0 -fmax)
3 = Motor speed (0 - Speed
max)
4 = Output current (0-InMotor)
5 = Motor torque (0-TnMotor)
6 = Motor power (0-PnMotor)
P13.2
AO1 minimum
0
1
0
310
Service
0 = 0V
1 = 2V
P13.3
AO1 Output
scale
0,0
1000,0
%
100.0
311
Service
Scaling factor
P13.4
AO1 filter time
0.00
10.00
s
0.10
308
Service
Filtering time of analogue out-
put signal.
0 = No filtering
Table 42: Group Analogue output.
Code
Parameter
Min
Max
Unit
Default
ID
Level
Description
P14.1
Parameters access level
0
2
0
115
Basic
0 = Basic
1 = Advanced
2 = Service
P14.2
Parameters lock
0
1
0
1805
Basic
0 = Edit Enabled
1 = Edit Disabled
Table 43: Group User interface.