Parameter description
vacon • 62
Service support: find your nearest Vacon service center at www.vacon.com
3
3.13
Analogue Output
P13.1 A
NALOGUE
OUTPUT
FUNCTION
Signal coupled to analogue output.
P13.2
A
NALOGUE
OUTPUT
MINIMUM
SIGNAL
0: 0V
1: 2V
P13.3
A
NALOGUE
OUTPUT
SCALING
Scaling factor.
P13.4
A
NALOGUE
OUTPUT
FILTER
TIME
Time constant of low pass filter.
Note: analogue output terminals are not accessible in standard Vacon 20X+D drive.
3.14
User interface
P14.1
P
ARAMETERS
ACCESS
LEVEL
See chapter 1
0: Basic
1: Advanced
2: Service
P14.2
P
ARAMETERS
LOCK
0: Edit enabled
1: Edit disabled
Selection
Selection name
Value corresponding to maximum output
0
Not used
output always fixed at 100%
1
Frequency reference
Max frequency(P3.2)
2
Output frequency
Max frequency(P3.2)
3
Motor speed
Motor nominal speed
4
Motor current
Motor nominal current
5
Motor torque
Motor nominal torque (absolute value)
6
Motor power
Motor nominal power (absolute value)
Table 48. Analogue output signals.