Table 121: Fieldbus Control Word
Bit
Descriptions
Value = 0 (FALSE)
Value = 1 (TRUE)
Bit 0
Stop request from Fieldbus
Start request from Fieldbus
Bit 1
Forward direction request
Reverse direction request
Bit 2
No action
Reset active faults and alarms (on rising
edge 0=>1)
Bit 3
No action
Force stop mode to Coasting
Bit 4
No action
Force stop mode to Ramping
Bit 5
No action
(normal deceleration ramp time)
Force drive to use fast deceleration ramp
time
(1/3 of normal deceleration time)
Bit 6
No action
Freeze drive frequency reference
Bit 7
No action
Force Fieldbus frequency reference to zero
Bit 8
No action
Force drive control place to Fieldbus con-
trol
Bit 9
No action
Force drive reference source to Fieldbus
reference
Bit 10
No action
Jogging Reference 1 activation
NOTE!
This will start the drive.
Bit 11
No action
Jogging Reference 2 activation
NOTE!
This will start the drive.
Bit 12
No action
Activate Quick Stop function
NOTE!
This will stop the drive according to set-
ting in parameter menu M3.9.5.
Bit 13
Reserved
Reserved
Bit 14
Reserved
Reserved
Bit 15
Reserved
Reserved
VACON · 192
MONITORING VALUE DESCRIPTIONS
9
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/