Selection
number
Selection name
Description
1002
Enabled mode
The drive resets all the faults and continues to operate at the
same speed until it is not possible
1234
Test mode
The drive does not automatically reset the faults, and the
drive stops when a fault occurs.
P3.17.2 FIRE MODE FREQUENCY SOURCE (ID 1617)
Use this parameter to select the frequency reference source when the Fire mode is active.
This parameter enables the selection of, for example, the AI1 or the PID controller as the
reference source when you operate the Fire mode.
P3.17.3 FIRE MODE FREQUENCY (ID 1598)
Use this parameter to set the frequency that is used when Fire mode is active.
The drive uses this frequency when the value of parameter P3.17.2 Fire Mode Frequency
Source is Fire Mode Frequency.
P3.17.4 FIRE MODE ACTIVATION ON OPEN (ID 1596)
Use this parameter to select the digital input signal that activates the Fire Mode function.
If this digital input signal is activated, an alarm shows on the display, and the warranty
becomes void. The type of this digital input signal is NC (normally closed).
It is possible to try the Fire mode with the password that activates the Test mode. Then the
warranty stays valid.
NOTE!
If Fire mode is enabled, and you give the correct password to the parameter Fire
Mode Password, all the Fire mode parameters become locked. To change the Fire
mode parameters, change the value of P3.17.1 Fire Mode Password to 0 first.