Normal
Start
Run
Enable
Run
Interlock 2
Fire Mode
Activation
(Close contact)
Motor Speed
Stopped
Normal
Speed
Fire Mode
Speed
Run
Interlock 1
Fig. 87: The Fire mode function
P3.17.5 FIRE MODE ACTIVATION ON CLOSE (ID 1619)
Use this parameter to select the digital input signal that activates the Fire Mode function.
The type of this digital input signal is NO (normally open). See the description for P3.17.4 Fire
Mode Activation on Open.
P3.17.6 FIRE MODE REVERSE (ID 1618)
Use this parameter to select the digital input signal that gives a command for reverse
rotation direction during the Fire Mode.
The parameter does not have an effect in normal operation.
If it is necessary for the motor to operate always FORWARD or always REVERSE in Fire
Mode, make a selection of the correct digital input.
DigIn Slot0.1 = always FORWARD
DigIn Slot0.2 = always REVERSE
V3.17.7 FIRE MODE STATUS (ID 1597)
This monitoring value shows the status of the Fire mode function.
V3.17.8 FIRE MODE COUNTER (ID 1679)
This monitoring value shows the number of the fire mode activations.