NOTE!
If you start the application wizard from the Start-up wizard, the wizard goes directly
to step 11.
1
Set a value for P3.1.2.2 Motor Type (so that it agrees
with the nameplate of the motor)
PM motor
Induction motor
Reluctance motor
2
Set a value for P3.1.1.1 Motor Nominal Voltage (so
that it agrees with the nameplate of the motor)
Range: Varies
3
Set a value for P3.1.1.2 Motor Nominal Frequency
(so that it agrees with the nameplate of the motor)
Range: 8.00…320.00 Hz
4
Set a value for P3.1.1.3 Motor Nominal Speed (so
that it agrees with the nameplate of the motor)
Range: 24…19200 rpm
5
Set a value for P3.1.1.4 Motor Nominal Current (so
that it agrees with the nameplate of the motor)
Range: Varies
If you set Motor Type to Induction Motor, you see the next step. If your selection is PM Motor,
the value of parameter P3.1.1.5 Motor Cos Phi is set to 1.00, and the wizard goes directly to
step 7.
6
Set a value for P3.1.1.5 Motor Cos Phi (so that it
agrees with the nameplate of the motor)
Range: 0.30…1.00
7
Set a value for P3.3.1.1 Minimum Frequency Refer-
ence
Range: 0.00…P3.3.1.2 Hz
8
Set a value for P3.3.1.2 Maximum Frequency Refer-
ence
Range: P3.3.1.1…320.00 Hz
9
Set a value for P3.4.1.2 Acceleration Time 1
Range: 0.1…300.0 s
10
Set a value for P3.4.1.3 Deceleration Time 1
Range: 0.1…300.0 s
11
Set a value for P1.36.1 Motor Potentiometer Ramp
Time
Range: 0.1…500.0 Hz/s
12
Set a value for P1.36.2 Motor Potentiometer Reset
0 = No Reset
1 = Stop State
2 = Power Down
The Motor Potentiometer application wizard is completed.
2.7
MULTI-PUMP WIZARD
To start the Multi-pump wizard, make the selection Activate for parameter B1.1.3 in the
Quick setup menu. The default settings tell you to use the PID controller in the one
VACON · 60
WIZARDS