9. The STOP button on the keypad is
pushed and the frequency that is fed to
the motor goes to 0. (This signal only
works if the value of P3.2.3 Keypad Stop
Button is Yes.)
10. Before the drive can start, you must
open and close CS1 again.
11. CS1 becomes inactive and the frequency
goes to 0.
P3.2.7 I/O B START/STOP LOGIC (ID 363)
Use this parameter to control the start and stop of the drive with the digital signals.
The selections can include the word 'edge' to help you prevent an accidental start.
See P3.2.6 for more information.
P3.2.8 FIELDBUS START LOGIC (ID 889)
Use this parameter to set the fieldbus start logic.
The selections can include the word 'edge' to help you prevent an accidental start.
Selection
number
Selection name
Description
0
A rising edge is necessary
1
State
P3.2.9 START DELAY (ID 524)
Use this parameter to set the delay between the start command and the actual start of the
drive.
P3.2.10 REMOTE TO LOCAL FUNCTION (ID 181)
Use this parameter to set the selection of copy settings when you go from Remote to Local
(keypad) control.
Selection
number
Selection name
Description
0
Keep Run
1
Keep Run & Reference
2
Stop
PARAMETER DESCRIPTIONS
VACON · 221
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
10