A maintenance counter tells you that the maintenance must be done when the counter value
goes above the set limit.
P3.16.2 COUNTER 1 ALARM LIMIT (ID 1105)
Use this parameter to set the alarm limit for the maintenance counter.
When the value of the counter goes above this limit, a maintenance alarm occurs.
P3.16.3 COUNTER 1 FAULT LIMIT (ID 1106)
Use this parameter to set the fault limit for the maintenance counter.
When the value of the counter goes above this limit, a maintenance fault occurs.
P3.16.4 COUNTER 1 RESET (ID 1107)
Use this parameter to reset the maintenance counter.
P3.16.5 COUNTER 1 DI RESET (ID 490)
Use this parameter to select the digital input that resets the value of the Maintenance
Counter.
10.18
FIRE MODE
When Fire mode is active, the drive resets all faults that occur and continues to operate at
the same speed until it is not possible. The drive ignores all commands from the keypad,
fieldbuses, and the PC tool. It only obeys the signals Fire Mode Activation, Fire Mode
Reverse, Run Enable, Run Interlock 1, and Run Interlock 2 from I/O.
The Fire mode function has 2 modes, the Test mode and the Enabled mode. To make a
selection of a mode, write a password in parameter P3.17.1 (Fire Mode Password). In the
Test mode, the drive does not automatically reset the faults, and the drive stops when a fault
occurs.
It is also possible to configure Fire mode with the Fire mode wizard, which you can activate in
the Quick Setup menu with parameter B1.1.4.
When you activate the Fire mode function, an alarm shows on the display.
CAUTION!
The warranty is void if the Fire mode function is activated! You can use Test mode
to test the Fire mode function and the warranty stays valid.
P3.17.1 FIRE MODE PASSWORD (ID 1599)
Use this parameter to enable the Fire Mode function.
NOTE!
All other Fire Mode parameters will be locked when the Fire Mode is enabled and
correct password is set in this parameter.
PARAMETER DESCRIPTIONS
VACON · 317
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/