READY
FAULT
ALARM
STOP
RUN
KEYPAD
1/O
REV
FWD
BUS
A
B
C
Fig. 46: The Analogue inputs menu in the text display
A. The text display
B. The name of the parameter
C. The value of the parameter, that is, the
set analogue input
In the standard I/O board compilation, there are 2 analogue inputs available: the slot A
terminals 2/3 and 4/5.
Input type (graphi-
cal display)
Input type
(text dis-
play)
Slot
Input #
Explanation
AnIN
AI
A
1
Analogue input #1 (terminals 2/3) on a board in
Slot A (standard I/O board).
AnIN
AI
A
2
Analogue input #2 (terminals 4/5) on a board in
Slot A (standard I/O board).
The location of the parameter P3.5.2.1.1 AI1 Signal Selection is the menu M3.5.2.1. The
parameter gets the default value AnIN SlotA.1 in the graphical display or AI A.1 in the text
display. The target input for the signal of the analogue frequency reference AI1 is then the
analogue input in the terminals 2/3. Use the dip switches to set the signal to be voltage or
current. See the Installation manual for more data.
Index
Parameter
Default
ID
Description
P3.5.2.1.1
AI1 Signal Selec-
tion
AnIN SlotA.1
377
To change the input from AI1 to, for example, the analogue input on your option board in slot
C, obey these instructions.
PARAMETER DESCRIPTIONS
VACON · 245
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
10