M1
M2
M3
M4
M5
A
ID428 =FALSE
Fig. 82: The interlock logic 2
A. Starting order of motors
If you add Motor 3 again (you set the value of P3.5.1.36 to CLOSED), the system puts Motor 3
last in the sequence: 1, 2, 4, 5, 3. The system does not stop, but continues to operate.
M1
M2
M4
M5
M3
A
ID428 = TRUE
Fig. 83: The interlock logic 3
A. New starting order of motors
When the system stops or goes to sleep mode for the next time, the sequence changes back
to 1, 2, 3, 4, 5.
P3.15.3 INCLUDE FC (ID 1028)
Use this parameter to include the controlled motor/pump in the autochange and interlock
system.
If the controlled motor/pump not included, the controlling motor is always motor number 1.
Please refer to the manual for wiring diagrams in both cases.
VACON · 310
PARAMETER DESCRIPTIONS
10