Table 96: Setpoints of the external PID controller
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.14.2.1
Keypad Setpoint 1
0.00
100.00
Varies
0.00
1640 See P3.13.2.1
P3.14.2.2
Keypad Setpoint 2
0.00
100.00
Varies
0.00
1641 See P3.13.2.2
P3.14.2.3
Setpoint Ramp Time
0.00
300.00
s
0.00
1642 See P3.13.2.3
P3.14.2.4
Select Setpoint
Varies
Varies
DigIN
Slot0.1
1048 OPEN = Setpoint 1
CLOSED = Setpoint 2
P3.14.2.5
Setpoint Source 1
Selection
0
32
1
1643
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 =ProcessDataIn1
10 =ProcessDataIn2
11 =ProcessDataIn3
12 =ProcessDataIn4
13 =ProcessDataIn5
14 =ProcessDataIn6
15 =ProcessDataIn7
16 =ProcessDataIn8
17 = Temperature Input
1
18 = Temperature Input
2
19 = Temperature Input
3
20 = Temperature Input
4
21 = Temperature Input
5
22 = Temperature Input
6
23 = Block Out.1
24 = Block Out.2
25 = Block Out.3
26 = Block Out.4
27 = Block Out.5
28 = Block Out.6
29 = Block Out.7
30 = Block Out.8
31 = Block Out.9
32 = Block Out.10
PARAMETERS MENU
VACON · 153