P3.10.2 RESTART FUNCTION (ID 719)
Use this parameter to select the start mode for the Automatic reset function.
P3.10.3 WAIT TIME (ID 717)
Use this parameter to set the wait time before the first reset is done.
P3.10.4 TRIAL TIME (ID 718)
Use this parameter to set the trial time for the automatic reset function.
During the trial time, the automatic reset function tries to reset the faults that occur. The
time count starts from the first automatic reset. The next fault starts the trial time count
again.
P3.10.5 NUMBER OF TRIALS (ID 759)
Use this parameter to set the total number of autoreset trials.
If the number of trials during the trial time is more than the value of this parameter, a
permanent fault shows. If not, the fault goes out of view after the trial time is completed.
The fault type does not have an effect on the maximum number of trials.
Fault trigger
Autoreset
Trial time
Wait
time
Wait
time
Wait
time
ID717
Reset 1
Reset 2
Trial time
ID718
Fault active
Alarm
Number of trials: (ID759 = 2)
ID717
ID717
Fig. 63: The Automatic reset function
P3.10.6 AUTORESET: UNDERVOLTAGE (ID 720)
Use this parameter to enable the automatic reset after an undervoltage fault.
VACON · 286
PARAMETER DESCRIPTIONS