Close Control Regulation Program
06MC0071@00B0110
01/10/2012
49
This screen, displayed only when the mechanical expansion valve is
fitted, is used to establish the activation of the low pressure alarm by
the pressure switch connected to ID6, setting:
Alarm Delay After Compr. ON: alarm BP activation delay time from
compressor ON
Alarm Delay Normal Working: alarm BP activation delay time during
normal operation
This screen is used to set the parameters for the operation of the
humidifier inside the unit, defining:
Humid. Model.: model installed;
V.: operating voltage;
TAM: model of current transformer used
Steam Cap.: number of kg of steam generated in 1 hour;
Nom.Current: rated current;
Max Steam Prod.: maximum rated percentage of steam to deliver
Timed drains enable: enables the procedure for draining the cylinder
to avoid the formation of scale inside
This screen, displayed only if the cylinder cleaning procedure is
enabled, is used to set:
Timed drains after number of startups: number of humidifier starts
before draining the cylinder;
Drain Time: cylinder drain procedure activation time
This screen, displayed only if the multifunction digital input is enabled,
is used to set:
Off Unit on Alarm: enables the shutdown of the unit if the flood alarm
is activated;
Valve Closed on Al.: enables the closing of the water valve if the
flood alarm is activated;
This screen is used to set:
ON/OFF mode Via input contact: enables unit on/off via the
multifunction digital input;
ON/OFF mode only Via serial: enables unit on/off from BMS;
Motorized Damper: enables operation of the damper;
Opening Time: damper opening time. During this period the start of
the fan and the air flow alarm are ignored.