Close Control Regulation Program
06MC0071@00B0110
01/10/2012
59
Number of cylinder operating hours exceeded. Replace the cylinder
This may be shown in the following two cases:
Fill phase:
if the maximum fill time has elapsed
if the current measured does not reflect normal fill operation
Pre-wash status:
if during the fill phase the water level does not touch the high level
electrodes within the maximum fill time
Warning only
SENSOR ALARMS
These are activated when there is a malfunction of the sensors, or they have been incorrectly connected to the
main board. If one of these alarms is activated, check the exact configuration set, that the sensor is present and
that the connections have been made and are operating correctly.
Activated following an error signal from the sensor which is connected,
disabling the unit operation linked with the reading.
Causes the compressors and electric heaters to switch off, keeping
only the fans switched on.
Disables the free-cooling operation control (only ES units)