Close Control Regulation Program
06MC0071@00B0110
01/10/2012
67
UPLOAD FILE
UPLOAD APPLICATION
In all 16-bit UpCO system controllers the resident software can be updated from a PC. To do this, UNIFLAIR Spa provides the
WinLoad32.exe program and an RS485 serial converter for the UpCO. The special driver needs to be installed on the PC, again
supplied by UNIFLAIR Spa.
In general, the sequence of operations for establishing communication between Winload in graphic mode and UpCO is as
follows:
1. connect the serial converter or USB to the PC and to the UpCO;
2. open the Winload program on the PC, by double clicking the icon after having activated any options via the command
line;
3. on the main screen, set the serial port on the PC that the serial converter is connected to and the pLAN address of the
UpCO in question;
4. power up the UpCO;
5. wait for the controller to come online, as indicated at the bottom left of the main screen;
6. then select the desired directory (Application) on the main page to perform the desired operation.
7. click on the Upload function key and wait for the end of the upload operation defined by >>OK – UPLOAD
COMPLETED SUCCESSFULLY<<;