Close Control Regulation Program
06MC0071@00B0110
01/10/2012
63
CONFIGURATION
NUMERICALS
PARAMETERS
PARAMETER DESCRIPTION
DEF. PARAMETER
DESCRIPTION VAL. DEF. MIN. MAX.
High Water Temp. (C1/C2)
A
DELAY SETTINGS
Low Air Pressure
A
Integral Time
s
600
0
2000
AFPS: Expansion Board
A
Anti-hunting time constant
min
1
0
30
CW Dehumid. Failure (C1/C2)
A
Unit Start Up Delay At Power On
s
0
0
300
D.C.: Expansion Board
A
Regulation Transient
s
60
15
200
Supply Frequency
A
Fan Off delay
s
10
10
60
Wrong Phases Seq.
A
Temp/Hum.Alarms Delay
Room Temp.Sensor
A
After Power ON
min
10
0
99
Room Humid.Sensor
A
Normal Working
s
60
0
999
Delivery Temp. Sensor
A
Wrong Phases Sequence Min.OFF Time
s 60 5 999
Outdoor temp. Sensor
A
OTHER RESOURCES
Water IN Temp. Sensor (C1/C2)
A
Motorized damper time
s
120
20
300
Water OUT Temp. Sensor (C1/C2)
A
Backlight Time
s
300
30
999
Hot Water Temp. Sensor
A
Buzzer On Time
min
5
1
999
Air Pressure Sensor
A
SENSOR ADJUSTMENT
Loss of Water Flow
A
Adjustment
°C
0.0
-9.9
+9.9
Smoke/Fire A
COMPRESSOR
Flooding A
Transient
limit
LP
bar
0.2
0.1
5.0
Local Network
A
LP Alarm normal limit
bar
2.0
0.9
5.0
Humidifier Failure
A
LP Alarm differential
bar
1.3
0.1
5.0
External Sensors
A
LP Alarm after compress. ON
s
180
30
240
High Delivery Temp
A
LP Alarm at normal work
s
6
2
10
Unit Run Hours
A
Minimum OFF compr. time
s
60
60
600
Filter Run Hours
A
Minimum OFF compr. time
s
60
0
999
Compress.Run Hours
A
Minimum time 2 starting
s
360
360
600
El.Heaters Run Hours
A
AFPS
Humidif.Run Hours
A
Air trasducer press Range Begin.
Pa
0
-6250
6250
Alarm By ID2
A
Air trasducer press Range End.
Pa
100
0
6250
Alarm By ID4
A
Delta Input Filter
Pa
4.0
-9.9
+9.9
Alarm By ID6
A
Time Input Filter
s
1
0
99
STAND-BY ROTAT. ALARMS
Min. speed fan
%
55
40
100
Loss of Air Flow
Yes
Max. speed fan
%
100
40
100
Clogged
Filters
No Setpoint
Pa
20.0
0
6250
Heaters Overheating
Yes
Dead Band
Pa
0.0
0
6250
EEPROM Failure
Yes
Regul. band
Pa
160.0
0
9999
Wrong
Password
No Integral
time
s
40
0
999
High Air Flow
Yes
Derivat. Time
s
0
0
999
High Cond.Pressure
Yes
Alarm level
Pa
15.0
0
6250
Low Evap.Pressure
Yes
Alarm delay
s
60
0
999
EXV Valve Failure
No
Energy Saving SETTINGS
High Room Temp.
No
Energy Saving Temp.
°C
8.0
5.0
24.0
Low Room Temp.
No
Summer Temp.
°C
28.0
15.0
40.0
High Room Humidity
No
Actived radcooler Set point
°C
28.0
15.0
40.0
Low Room Humidity
No
ON Radcooler fan at E.S.
°C
8.0
1.0
15.0
High Water Temp. (C1/C2)
No
E.S. Set point (Room T.-Water T.)
°C
6.0
1.0
15.0