Close Control Regulation Program
06MC0071@00B0110
01/10/2012
65
CONFIGURATION
NUMERICALS
PARMETERS
PARAMETER DESCRIPTION
DEF. PARAMETER
DESCRIPTION VAL. DEF. MIN. MAX.
SUPERVISION
LOP Protection Integral Time
s
15.0
0
600
Serial Address
01
LOP Protection Integral Time Auto
s
1.5
-
-
Serial Speed (1200-19200)
1200
Dehumid. SH Set
°C
20.0
2.0
40.0
Protocol Std
Dehumid.
LOP
limit
°C
2.0
-50.0
70.0
Twin Cool CALIBRATION
Enabled CW working
Also On DX Alarm
Yes
Only By ID Contact
No
Only By Serial
No
Cooling Water CALIBRATION
Sensor of regulation
RoomT.
Valve Off of the alarm High water Temp.
Yes
Enabled Change Set Chiller of Dehumi.
No
EXV VALVE
Valve type
E2V
Refrigerant Type
R407C
Low SH Protection
Yes
MOP Protection
Yes
LOP Protection
Yes
Manual open Step
No
LOW PRESSURE SETTINGS WITH THE REFRIGERANT TYPE
R22 R407C
R410A
R134a MIN MAX
Transient
limit
bar
0,2 0,2 0,5 0,2 0,1 5,0
Normal
limit
bar
2,0 2,0 4,6 1,0 0,9 5,0
Alarm
differential
bar 1,3 1,3 2,0 1,3 0,1 5,0
Alarm
delay
after
compr.
ON
s 180 180 180 180 30 240
Alarm
delay
normal
working
s 06 06 06 06 02 10
LOW PRESSURE TRASDUCER RANGE
Range
Begin:
bar
-1,0 -1,0 -0,4 -1,0 -9,9 99,9
Range
Ending:
bar
9,1 9,1 34,3 9,1 0,0 99,9