Close Control Regulation Program
64 06MC0071@00B0110
01/10/2012
CONFIGURATION
NUMERICALS
PARAMETERS
PARAMETER DESCRIPTION
DEF. PARAMETER
DESCRIPTION VAL. DEF. MIN. MAX.
Low Air Pressure
No
Twin Cool SETTINGS
AFPS: Expansion Board
No
CW enable Setpoint
°C
7.0
7.0
25.0
Room Temp.Sensor
Yes
CW deactivation Setpoint
°C
3.0
0.0
9.9
Humidity Sensor
Yes
Cooling Water SETTINGS
Deliv.Temp.Sensor
No Dehumidification
set
point
°C
7.0
5.0
20.0
Outdoor Temp.Sensor
No
High water temp. alarm (C1/C2)
°C
15.0
5.0
80.0
Water In Temp.Sens. (C1/C2)
No
Open valve at alarm (C1/C2)
%
0
0
50
Water Out Temp.Sens. (C1/C2)
No
P1 Dual Coil
%
100
0
100
Hot Water Temp.Sens.
No
P2 Dual Coil
%
0
0
100
Air Pressure Sensor
No
Hot Water Coil set point
°C
40
25
60
Loss of Water Flow
No
EXV VALVE
Flooding
No MOP
Set
°C
14.0
-50.0
70.0
External Sensors
No
LOP set
°C
02.0
-50.0
70.0
Humidifier Failure
Yes
Pressure Probe Range Begin.
bar
-01.0
-99
999
High Delivery Temp.
No
Pressure Probe Range Ending
bar
09.1
0
999
CW Dehumid.Failure (C1/C2)
No
Pressure Probe Offset
bar
0.0
-9.9
+9.9
D.C.: Expansion Board
No
Temperature Probe Offset
°C
0.0
-9.9
+9.9
Alarm By ID2
No
Low SH
s
120
0
600
Alarm By ID4
No
High Suction Temp.
s
0
0
600
Alarm By ID6
No
LOP Failure
s
0
0
600
ALARMS RESET MODE
MOP
Failure
s
0
0
600
High Room Temp.
Auto
Press. Probe Failure after comp. ON
s 20 0 99
Low Room Temp.
Auto
Press. Probe Failure at norm. work
s
10
0
99
High Room Humidity
Auto
Manual open Step
n°
265
0
2625
Low Room Humidity
Auto Closing
Backsteps
n°
5
0
100
High Water Temp. (C1/C2)
Auto
Superheat set
°C
6.0
2.0
40.0
Loss of Air Flow
Man.
Superheat set Auto
°C
6.0
-
-
High Air Flow
Man.
Dead Zone
°C
0.0
0
99
Low Evap.Pressure
Auto
Dead Zone Auto
°C
0.0
-
-
EEV Valve Failure
Auto
Prop. Gaing.
3.0
0
999
External Sensors
Man.
Prop. Gaing. Auto
2.6
-
-
Loss of Water Flow
Man.
Integral Time
s
30
0
999
Humidifier Failure
Man.
Integral Time Auto
s
35
-
-
Smoke-Fire Man.
Derivat.
Time s
1.5
0
999
Alarm By ID2
Man.
Derivat. Time Auto
s
1.5
-
-
Alarm By ID4
Man.
Max Suction Temp.
°C
30.0
0
999
Alarm By ID6
Man.
Max Suction Temp. Auto
°C
20.0
-
-
High Delivery Temp.
Auto
Circ/EEV Ratio.
%
50
0
100
Low Air Pressure
Auto
Low Sheat protection limit
°C
0.5
-0.4
21.0
AFPS: Expansion Board
Auto
Low Sheat protection limit Auto
°C
2.0
-
-
High Wat.T.to Deh. (C1/C2)
Auto
Low Sheat protection Integral Time
s
15.0
0
300
Dual Coil: Exp.Board.
Auto
Low Sheat protec. Integ. Time Auto
s
0.8
-
-
MOP Protection Start-up delay
s
30
0
600
MOP Protection Start-up delay Auto
s
30
-
-
MOP Protection Integral Time
s
3.5
0
999
MOP Protection Integral Time Auto
s
2.5
-
-