Close Control Regulation Program
44 06MC0071@00B0110
01/10/2012
This screen is used to set:
T+H Al. Delay’: delay in signalling room alarms when starting the unit
and in normal operation.
Wrong Phases Sequence or Phase Loss: minimum unit OFF time if
the alarm is activated.
This screen is used to change the access passwords:
- for the settings ("SETTINGS" password);
- for the configuration ("CONFIGURATIONS" password or
"SERVICE" password).
Since access to the HARDWARE menu is denied unless the
corresponding password is known, the new password should be
written down before changing the old one.
This screen is used to set:
Anti-Hunting Time Constant: control time constant;
Delay Com. Error: delay for the communication error between the unit
and the Master Control;
Start Com. Trans.: initial communication transient
The last line indicates the status of communication between the unit
and the Master Control.