- 36 -
14. Adjusting the analog output (option)
! < Caution >
※It's being adjusted according to the analog output option, but when being
adjusted by yourself, please setting it with the following procedure.
When a power supply is supplied while is pressing Display Key,an analog
output adjustment mode setting.
* Displayed when analog output option is selected (AI/AV3-5 type).
Operation key
Indication
Procedure
A B C D E
1○
2○ A n A
T○
When a power supply is supplied while is
pressing Display Key, "AnA" is displayed.
A B C D E
1○
2○ A n - 1
T○
When Mode Key is pressed, "An-1" is displayed.
An analog output adjustment (minimum)
is performed.
A B C D E
1○
2○ 0 4 A 8
T○
(The bit values)
Please adjust the bit value to the output
minimum value of "AI,AV3-5".
When Dispay Key is pressed, the bit values
increases.
When Shift Key is pressed, the bit values
decreases.
〔The variable range is 0000-3FFF.〕
A B C D E
Measured value
After adjusting the setting, use Reset Key to
register the lower bit values .
A B C D E
1○
2○ A n - 2
T○
When Mode Key is pressed, "An-2" is displayed.
An analog output adjustment (maximum)
is performed.
A B C D E
1○
2○ 3 b 5 8
T○
(The bit values)
Please adjust the bit value to the output
maximum value of "AI,AV3-5".
When Display Key is pressed, the bit values
increases.
When Shift Key is pressed, the bit values
decreases.
〔The variable range is 0000-3FFF.〕
A B C D E
Measured value
After adjusting the setting, use Reset Key to
register the upper bit values .
A B C D E
1○
2○ Measured value
T○
When Mode Key is pressed for more than
2 seconds, a display returns to measure-
ment indication.
DISP
RST
RST
MODE
MODE
MODE
MODE
MODE