- 17 -
≪2. Contents of the each mode and set value≫
Mode No. Ratemeter : Setting of scaling data
1
A B C D E
1. 1 0 0 0
Scaling data
0001-9999
(Do not specify 0000.)
Input scaling is performed for the rate meter reading. By specifying
the scaling data and the exponential value (a minus power of 10),
the scaling ratio per pulse can be set. The exponential value
(a minus power of 10)is set in mode No.2.
〔Ex.〕Using a flow meter which emits 1 pulse per 1.234mL,
the cumulative total flow in liters can be expressed using
the following conversion.
1.234mL 0.001234L 1234 × 10
-6
Scaled to the desired unit (L)
4 digits Exp. value
A B C D E
Mode No.1 1.1 2 3 4
A B C D E
Mode No.2 2.6 * * *
Please refer to the next page for other property examples.