displayed. The menu choices Dry Contact Alarm Relay Setup and Aux Output Setup are discussed
below.
4.6.2 CP-3600(+) Relay 1+2 Programming
To program dry contact relays 1+2, highlight Dry Contact Alarm Relay Setup and press enter. The
following screen will be displayed.
Alarm relays 1+2 are programmed in the same manner as the NAC relays as explained in section 4.5.2
except there is no “On” option and the relay Off selection is limited to Reset or Signal Silence only.
4.6.3 Auxiliary Programming
To program the AUX output, highlight AUX Output Setup and press enter. The AUX programming menu
selections will be shown. You can choose any
one
of the alarm priorities A, B, C, or D to activate the
output. The alarm priorities are explained in section 4.4.4 of this manual. Select alarm priority A for UL
installations. An X in the “On Signal” field means the output is not programmed to activate. The output
will be activated when an alarm signal is received from a device whose priority matches the alarm
priority selection for the output. Once the output is activated, it can only be deactivated or turned off
manually by pressing a button. Pressing the RESET button will always deactivate the output. In addition
to the RESET button, the SIGNAL SILENCE button can also be programmed into the “Off Button” field
to deactivate the output. Selecting Reset will keep the output activated until the RESET button is
pressed. Select Reset as the off button for UL installations.
To change the “On Signal” field, move the cursor to that field and press ENTER. Use the UP/DOWN
buttons to select the alarm priority then press ENTER to exit edit mode. Press the save soft key to save
your changes or the cancel soft key to abort the changes.
Important: Only alarms will activate this output. Any device programmed for sprinkler
supervisory as detailed in sections 4.4.4 and 4.7 of this manual will NOT activate the Auxiliary
output even if programmed to do so.
C P - 3 6 0 0 D R e l a y S e t u p
D e f a u l t s N e x t
D r y C o n t a c t A l a r m R e l a y 0 1
N
N A C R L Y 0 1 “ O n ” Z o n e s
# 1 # 2 # 3 # 4 # 5
Z o n e 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Z o n e s 0 0 0 1 - 0 8 9 9 , 1 0 0 0 - 1 5 0 0 F o r A l a r m s
Z o n e s 0 9 0 0 - 0 9 9 9 F o r T r o u b l e s
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
R e l a y 0 1 “ O f f ” B u t t o n s
R e l a y O f f R e s e t o n l y