Tyco Fire & Security CWSI CP-3600 Скачать руководство пользователя страница 13

P/N CWSI-IM-C3K6 Rev. F 

 

© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision 
date and are subject to change without notice.

  

13

Section 3 - Installation 

 

3.1 Proper Installation Order 

The following steps when performed in the listed order will result in a trouble free 
installation: 

1. Site Signal Survey 
2.  Control Panel Installation and Basic Programming 
3.  Device and Repeater Enrollment and installation  
4.  Control Panel Site Specific Programming 
5.  Entire installation test 

 

3.2 Preparing the Installation Site 

Prior to the installation of a CP-3600(+) system a signal survey must be performed by a factory trained 
technician or authorized dealer. The signal survey determines the location of the CP-3600(+), 
repeaters, and initiating device transmitters. Refer to the Signal Survey section of this manual for the 
proper method to conduct a signal survey. The completed survey becomes the blueprint layout for the 
actual installation. When conducting a survey keep in mind the following limitations for each CP-3600(+) 
installation: 

1. Maximum number of devices including repeaters is 2048 on the CP-3600+. The CP-3600 is limited 

to 1024.  

2. Maximum number of repeaters between an alarm device and any notification appliance/facp in an 

installation is 30. This limitation insures that the UL and NFPA 10 second alarm requirement is met.  

3. Maximum number of devices per repeater or direct to the CP-3600(+) is 100. A repeater will 

automatically reject any devices in excess of 100 units that try to report directly to it. This is only a 
per repeater limitation not a system limitation. 

During the survey locate A/C repeaters and CP-3600(+) control panel close to available 120/240 Vac 
uninterruptible power. All CP-3600(+) connections must be installed in conduit. When connecting 
primary A/C power always follow: 
 
1- National Fire and Electrical Codes (NFPA 72 and NFPA 70) 
2- Local Electrical and Fire Code requirements 
3- Local AHJ (Authority Having Jurisdiction) requirements 

WARNING: Make sure A/C supply is turned OFF prior to connecting the CP-3600(+) panel. 
 

3.3 Receiving and Unpacking the Equipment 

Upon receiving the equipment, the carton should be inspected for damage, which may have occurred 
during shipment. Each package should be checked against the packing slip for completeness. 
Differences should be reported to CWSI immediately. If any product is suspected of damage it should 
be checked for proper operation or returned to CWSI.  
 

3.4 Installing the CP-3600(+) 

WARNING: This equipment must be professionally installed by factory trained personnel. Use 
of an antenna other than listed in the compatibility section of this manual may be harmful to 
persons, void FCC or damage the equipment. After conducting a signal survey the CP-3600(+) 
can be mounted in its intended location. Refer to the signal survey section of this manual for 

Содержание CWSI CP-3600

Страница 1: ...ights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice CP 3600 WIRELESS FIRE ALARM CONTROL PANEL OPERATING and...

Страница 2: ...curate and reliable at the time of printing Known corrections or omissions may be found on errata sheets included in the various product manuals However CWSI a Tyco Fire Security GmbH Company CWSI may...

Страница 3: ...ng the Installation Site 13 3 3 Receiving and Unpacking the Equipment 13 3 4 Installing the CP 3600 13 3 4 1 Enrolling Devices Annunciators and Repeaters 17 3 4 2 Installing the Annunciators Repeaters...

Страница 4: ...Audible Notification Device Tandem Control Menu 43 4 8 3 Programming Audible Notification Tandem Device Manual Activation and Deactivation 43 4 8 4 Remote Reset Feature 44 4 9 Unknown and Ignored Unit...

Страница 5: ...s 63 6 2 8 System and Programming Information 65 6 2 9 Accessing the System Info Screen 66 6 2 10 Accessing the Programming info Screen 66 SECTION 7 DIGITAL ALARM COMMUNICATORS 69 7 1 Silent Knight Mo...

Страница 6: ...70 National Electrical Code The model CP 3600 is the first in a series of wireless fire annunciation and control panels manufactured by CWSI This system was designed and tested to comply with NFPA 72...

Страница 7: ...Listed Communicators making the CWSI CP 3600 a complete installation solution The system is designed with monitoring and emergency personnel in mind The LCD display provides easily identifiable pinpo...

Страница 8: ...Tandem detector control 24 or 60 hour battery standby time 24 Volt Class A B NAC circuits 4 N O alarm dry contact outputs 2 form C programmable dry contact alarm outputs 1 form C trouble output Auxili...

Страница 9: ...Class A Style Z or 2 Class B Style Y Field selectable Class A ratings 24 Volts DC 1 Amp Class B ratings 24 Volts DC 1 Amp each Regulated NAC Circuits Programmable Non power Limited 1 Class A Style Z...

Страница 10: ...bination Smoke Heat Detector Pull Station Model 310 Manual Pull Station Fire Transmitter Models 345 TS N O EOL Supervised Transmitter CO Detector Model 350 Carbon Monoxide Detector with Integral Sound...

Страница 11: ...oftware In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited...

Страница 12: ...CWSI IM C3K6 Rev F 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 12 Figur...

Страница 13: ...that the UL and NFPA 10 second alarm requirement is met 3 Maximum number of devices per repeater or direct to the CP 3600 is 100 A repeater will automatically reject any devices in excess of 100 units...

Страница 14: ...sted wire routing WARNING Make sure A C supply is turned OFF prior to proceeding with A C connection Connect the incoming A C supply to the black transformer flying leads and earth ground to the gray...

Страница 15: ...ject to change without notice 15 Typical Antenna Configurations Figure 1A Always perform the signal survey with the antenna that will be used on the repeater when it is installed It is recommended to...

Страница 16: ...ion The time shown is approximate and will vary based on the amount of devices and relays to be found and verified The initialization process could take an hour on a system with many devices and progr...

Страница 17: ...screen will appear Note The CP 3600 will remain in enrollment mode indefinitely until the BACK key is pressed or an alarm is received A trouble will not cause the system to exit enrollment mode Devic...

Страница 18: ...e devices annunciators and repeaters is completed 3 4 2 Installing the Annunciators Repeaters and Devices Warning All devices annunciators and repeaters must be enrolled as described in the previous s...

Страница 19: ...nel back to normal operation mode Various troubles may be reported while installing the devices annunciators and repeaters This is normal After all of the equipment is installed reset the panel If any...

Страница 20: ...CWSI IM C3K6 Rev F 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 20 Figur...

Страница 21: ...ude 4 Softkey Up Down Left Right Enter and Back buttons See figure 3 below for the location of these buttons The Up Down Left Right buttons are used for menu navigation and character number selection...

Страница 22: ...g is not performed within 3 minutes the CP 3600 will revert back to the main screen and any unsaved changes will be lost If an Alarm or Supervisory signal is received while in any menu the CP 3600 wil...

Страница 23: ...Time and Date Password Setup Config Basecode Setup Supervisory Setup Device Enrollment Ignored Units Unknown Units A V Device Tandem Controls CP 3600 Setup Relay Setup Device Edit Program Aux Output R...

Страница 24: ...is showing and you will have access to the menus If ENTER is pressed with any of the wrong characters showing or 4 numbers are not entered the field will clear and the entire password will have to be...

Страница 25: ...s this soft key to save the changes or CANCEL to abort all changes to the page If you press the BACK key without saving a screen will appear asking if you want to save Press the appropriate soft key a...

Страница 26: ...the ENTER key and the screen below will be shown The three menu items shown are important to verify and change if necessary before continuing to the system main screen and performing any other progra...

Страница 27: ...the AM PM field and set it When you have time correctly set press the ENTER key to stop edit mode Use the same procedure to set the date and the Auto Update DST setting When the DST is off the clock...

Страница 28: ...eception range of any device repeater or CP 3600 in the same or a different installation Warning You must verify that each CP 3600 in reception range of another has different base codes before enrolli...

Страница 29: ...ress ENTER Use the UP DOWN buttons to choose On or Off then press enter When you are done making the desired changes press the Save soft key to save the change and display the Initial Configuration Me...

Страница 30: ...d annunciators as described in the WRA 3 manual Any devices or repeaters that have not been previously edited will show the NEW UNIT text in the description field Use the UP DOWN keys to highlight the...

Страница 31: ...the CP 3600 and access the device edit list through the device edit menu choice 4 Use the UP DOWN keys to select the device s and or repeater s to be deleted and press the delete soft key 5 Confirm th...

Страница 32: ...se The fifth group 896 899 is the global zones group for tandem devices Only 899 is in use at this time for the model 301 smoke detectors The alarm zones 001 889 and 1000 1500 can be used to activate...

Страница 33: ...4 Alarm Priority Assignment The CP 3600 has 4 levels of alarm which can be assigned to initiating devices These alarm levels are referred to as A B C and D A is the highest priority and D is the lowe...

Страница 34: ...r or change a description access the device edit screen for the desired device Move the blinking cursor to the description field and press ENTER The description field will now be highlighted The legen...

Страница 35: ...d increment No two devices will have the same Point I D Point ID s 0001 0007 are reserved for the Keltron SDACT 2 The Point ID is only used for central station reporting when a Keltron SDACT 2 dialer...

Страница 36: ...ch of the 5 relays setting the desired activation and deactivation methods The screens are similar to the above except substitute the word repeater with wireless relay 4 5 2 CP 3600 NAC Repeater NAC R...

Страница 37: ...e same time Model 301 Tandem Smoke alarm sounders are silenced Strobe Reset may be selected where horns and strobes must be individually reset Use of these buttons must comply with NFPA and or local A...

Страница 38: ...box will be momentary when zone 890 is used Note Manual activation and deactivation relay options will be disabled on relays which have zone 890 entered 4 5 4 Audible Notification Device Programming...

Страница 39: ...ate The output will be activated when an alarm signal is received from a device whose priority matches the alarm priority selection for the output Once the output is activated it can only be deactivat...

Страница 40: ...sprinkler supervisory feature of the CP 3600 must be turned on as described in this section 3 Select the appropriate device type for the sprinkler supervisory transmitters as required for the applica...

Страница 41: ...an alarm will be transmitted when the detector senses smoke The model 302 is a self contained smoke detector with no sounder intended for installation in common areas The model 302 will transmit an al...

Страница 42: ...amming options available for the model 301 The first option is the use of alarm zone 899 This zone is a global alarm zone for the model 301 When an alarm on zone 899 is activated all of the model 301...

Страница 43: ...for Device On is None This means the tandem detector sounders in the installation will only be activated by zones The Horns On button can be selected to activate all tandem sounders To program the Hor...

Страница 44: ...owing reasons 1 The device was deleted from the CP 3600 without removing the battery and allowing it to show a test failure trouble first As soon as the device tries to check in it will be reported as...

Страница 45: ...eceiving unknown units that you cannot identify which may be from another installation the correct solution is to change the base code of your CP 3600 To move the device to the ignored list highlight...

Страница 46: ...know where the device is and there is no need for it to continue to send an unknown device trouble Devices can remain on the ignored list indefinitely Warning The CP 3600 will not respond to alarms s...

Страница 47: ...CWSI IM C3K6 Rev F 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 47 Figur...

Страница 48: ...ed communicator and proper connection The contacts are rated at 24Volts D C 1 Amp resistive Acceptable wire size for connection is 16 22awg 5 1 2 Trouble Contact TB3 Terminals 5 7 There is 1 form C tr...

Страница 49: ...ot supported This is a non power limited connection Power limited and non power limited circuits must be separated by at least 25 within the enclosure and run in different conduit Refer to figure 4 fo...

Страница 50: ...All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 50 Note The trouble form C relay output will not...

Страница 51: ...nt sensing technology and if the rated current draw is exceeded a NAC overload trouble signal will be displayed and the NAC circuit output will deactivate It will attempt to reactivate only if another...

Страница 52: ...N STROBE 6 GENTEX GEC3 24 WR WW HORN STROBE 4 GENTEX GEC24 177 WR WW HORN STROBE 3 WHEELOCK HSR HSW HORN STROBE 4 WHEELOCK DSM 12 24 R SYNC MODULE 1 SYSTEM SENSOR P2R P2W HORN STROBE 4 SYSTEM SENSOR M...

Страница 53: ...right side of the main CP 3600 board as shown in figure 4 This connector is for downloading WRA 3 programming information with the WRA 3 programming tool Refer to the WRA 3 manual for more information...

Страница 54: ...will cause the Alarm LED to flash again Resetting the CP 3600 will turn this LED off Supervisory This LED flashes when any unacknowledged Supervisory alarm condition is present on the CP 3600 It will...

Страница 55: ...ssing this button will acknowledge all unacknowledged supervisory alarms silence the internal piezo sounder and change the Supervisory LED from flashing to steady If a different device transmits a Sup...

Страница 56: ...n the LCD when this button is pressed while an alarm is present Pressing this button will also send a record to the button press log The Strobe Reset button must be programmed to perform any of these...

Страница 57: ...ion exists the sounder will annunciate the associated pattern for that condition The sounder will also reactivate if a different device other than the ones already acknowledged transmits an Alarm Supe...

Страница 58: ...al alarms supervisory or trouble signals Transmitter test signals are also logged during normal operation 6 2 3 Alarm Alarms can be generated by any of the compatible initiating devices listed in this...

Страница 59: ...visory display 2 The sounder will pulse once a second 3 The sprinkler Supervisory LED will flash once a second 4 Alarm Relay 3 will activate 5 Relay 1 Relay 2 and auxiliary outputs will not activate 6...

Страница 60: ...onds 3 The trouble LED will flash once a second 4 The form C trouble contact will activate Note The trouble contact will not activate on a dialer fault trouble 5 The event is stored in the trouble and...

Страница 61: ...eeds factory service This trouble can also be caused by products with incompatible firmware versions 4 Aux Circuit Can occur in a CP 3600 control panel Caused by an open in the wiring connected to the...

Страница 62: ...If this occurs the unit should be returned to the factory for repair 15 Unknown Unit Can occur when a device annunciator or repeater that is not enrolled is checking into the CP 3600 control panel Ref...

Страница 63: ...a 4 hour time period with no keypad buttons pressed Multiple occurrences of the same type signal from any one device will only be displayed once while in test If you want to test the same signal from...

Страница 64: ...ter pressing the log key the log menu will be displayed Use the UP DOWN keys to select the desired log to view The last selection is Clear Test Log Choose this option if you want to erase the contents...

Страница 65: ...ng info provides a summary of the current programming of the CP 3600 including NAC enrolled devices etc 12 33 20PM 08 14 09 Last Pg Pg Down A l l E v e n t L o g R e s e t 1 2 1 0 0 0 A M 0 1 0 2 0 9...

Страница 66: ...o of Repeaters The number of currently enrolled repeaters is shown here 7 No of Devices The number of currently enrolled devices is shown here 8 No of annun The number of currently enrolled annunciato...

Страница 67: ...d Repeaters This section includes all of the enrolled repeaters and their associated serial number Description and point ID 5 Relay Rules This section includes Relay and NAC programming for the enroll...

Страница 68: ...e a t e r s R e p e a t e r 0 4 c f 5 3 D e s c 2 n d F l o o r H a l l w a y P o i n t I D 0 0 0 9 R e l a y R u l e s R e p e a t e r 0 4 c f 5 3 N A C R L Y 0 1 Z o n e 1 1 0 0 0 Z o n e 2 0 0 0 0...

Страница 69: ...is power limited Always run power limited and non power limited wiring in separate conduit Maintain at least between power limited and non power limited wiring within each enclosure The CP 3600 N O A...

Страница 70: ...under on the 5104B CANNOT be silenced by pressing the ALARM ACK key on the CP 3600 or the Reset Silence switch on the communicator The 5104B will silence its sounder and fully reset only when the CP 3...

Страница 71: ...Installation Follow the instructions in the communicator manual for mounting the unit Note All wiring must be in conduit and contained within the same room Use one of the recommended power supplies t...

Страница 72: ...al station receiver Only one programming change will be required to allow the CP 3600 to be compatible with the SDACT 2 Access the Dialer Setup menu under the CP 3600 Setup screen Turn the Keltron Dia...

Страница 73: ...C contacts on the trouble relay will open causing a trouble transmission to be sent from Zone 4 on the SDACT 2 Note A dialer fault trouble will not activate the CP 3600 trouble relay Acknowledging th...

Страница 74: ...set FH Fire Alarm Restore Alarm C FA Fire Alarm Alarm C Reset FH Fire Alarm Restore Alarm C Supervisory FS Fire Supervisory Alarm C Supervisory Reset FV Fire Supervisory Restore All Troubles except A...

Страница 75: ...ion The CP 3600 can also be used to activate a UL 864 listed central station remote station transmitter using the dry contacts outputs Alarm A Alarm B Supervisory C and Trouble The trouble input on th...

Страница 76: ...CWSI IM C3K6 Rev F 2017 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice 76 Figure...

Страница 77: ...location of the transmitter being used Once the initial beep is heard the magnet can be removed while waiting for the confirmation signal Continue this until the one beep and two beep confirmation ton...

Страница 78: ...ransmitter One beep should be heard at the device and the repeater which received the survey signal followed by either a single beep or two beeps at the device only A single beep indicates an unaccept...

Страница 79: ...Enclosure 9 Enrollment 8 18 EOL Violation 61 F Features 8 G Ground Fault 61 H Hardware Failure 61 Horns On 56 I Ignored Device 45 Initiating Device 7 8 10 13 19 55 57 58 60 61 62 63 Installation 13 In...

Страница 80: ...0 63 Smoke Detector 7 8 48 62 Smoke Detector Silence 56 Soft Keys 56 Sounder 7 55 57 58 59 60 77 Specifications 9 Strobe Reset 56 Supervisory 7 48 49 58 59 Supervisory Ack 55 Survey Button 78 System T...

Страница 81: ...uble signals press the TROUBLE ACK button To view multiple pages of Trouble signals press the PAGE UP or PAGE DOWN soft keys To activate evacuation horns press the HORNS ON button To silence evacuatio...

Отзывы: