P/N CWSI-IM-C3K6 Rev. F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision
date and are subject to change without notice.
36
Highlight the repeater to program and press ENTER. The NAC’s on the CP-3600(+) panel can be
programmed by selecting Control Panel. If the number of repeaters spans more than one screen page
up and page down soft keys will be present. Use the page up and page down soft keys to locate the
desired repeater then press ENTER. The following screen will be shown for the selected repeater.
The screen will show the default selections unless the selected relay has been previously modified.
The top text line indicates the serial number of the repeater and the specific relay being programmed.
Programming the wireless relay is similar. Choose the wireless relay from the first screen then
advance through each of the 5 relays setting the desired activation and deactivation methods. The
screens are similar to the above except substitute the word repeater with wireless relay.
4.5.2 CP-3600(+) NAC, Repeater NAC, Relay Box, RM-5 and SR-5
Programming
Up to 5 different zones can be programmed per relay. The 5 zone fields can be edited as described in
4.4.3 for device zone assignment. Enter the zones programmed into any transmitters which are required
to activate the selected relay. When the repeater receives a signal from that transmitter the relay will
S e l e c t D e v i c e t o P r o g r a m
0 0 5 c 2 8 R E P E A T E R 3 r d F l r H a l l w a y
1 d c 4 4 8 W i r e l e s s R e l a y B a s e m e n t
U s e U P D O W N t o s c r o l l t h e n p r e s s E N T E R
2 b 5 5 9 0 C o n t r o l P a n e l
R e l a y S e t u p
D e f a u l t s P r e v N e x t
R e p e a t e r 0 0 5 c 2 8 – N A C R e l a y 0 1
N
N A C R L Y 0 1 “ O n ” Z o n e s
# 1 # 2 # 3 # 4 # 5
Z o n e 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Z o n e s 0 0 0 1 - 0 8 9 9 , 1 0 0 0 - 1 5 0 0 F o r A l a r m s
Z o n e s 0 9 0 0 - 0 9 9 9 F o r T r o u b l e s
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
N A C R L Y 0 1 “ O n / O f f ” B u t t o n s
R e l a y O n N o n e
R e l a y O f f S i g n a l S i l e n c e
Repeater
being
programmed
Relay being
programmed
Zone entry
fields
Keypad button
selections for
manually
activating and
deactivating
selected relay