2 Parts names and function
7
MOTOR STATUS LED
0 1
・・・
E F
The channel is shown.
CW LS
●
●
・・・
●
●
LED lights when CW direction limit switch is activated.
CW P
●
●
・・・
●
●
LED lights when CW direction pulse is output.
MF
●
●
・・・
●
●
LED lights when motor hold off signal is output.
HP
●
●
・・・
●
●
LED lights when Home Position limit switch is activated.
CCW P
●
●
・・・
●
●
LED lights when CCW direction pulse is output.
CCW LS
●
●
・・・
●
●
LED lights when CCW direction limit switch is activated.
LED of limit switch blinks when digital limit switch described at page 25 was turned on.
No.
Name
Function
13
JOG switch
Starts CW or CCW JOG operation. Motor drives just
JOG set pulse with one push. If you hold over 0.4
sec., motor drives while holding.
In SETUP mode, changes the page of setup function.
14
MODE button
Select the drive mode when pushing start button.
Bright LED mode is selected mode.
Drive mode changes every pushing.
15
cursor button
Move the cursor position with these keys.
Changes set data at SETUP mode with “CHG”
button.
16
DSPCHG button
Exchanges motor drive screen and mode disp. screen.
17
numeric keys
Entry the numeric data at SETUP mode.
Sign inversion with “+-” button, data input cancel
with “CLR” button.
If you push “CLR” button when turning on the
power, pulse value of all channels are reset to zero.
18
TIMING/OUT connector
(LEMO)
TTL level pulse signal or gate signal according to
pulse position data are output. See ”8 Timing out
signal output” (Page 54) in details.