41
*Backlash adjustment move
When you execute absolute or relative move, moves extra backlash adjustment value
before reaching the destination point.
For example, adjustment value is +500, moves destination point plus 500 point and
moves relative -500 value. Backlash adjustment move pattern is changed by sign of
adjustment value and motor move direction. Please see the example below.
Ex.1) Move direction is CW and adjustment value is positive
Ex.2) Move direction is CW and adjustment value is negative
If move direction is CCW, these two drive routine are exchanged.
Backlash adjustment value is checked and changed at Page 2 on SETUP mode or
this command.
<ch>: 0 ~ F(Hexadecimal) for channel
Command B?<ch>
Check the backlash adjustment value.
Reply
±
dddd (signed 4 digit decimal.)
Example B?3 Reply: +0500 Backlash adjustment value of CH3 is 500.
Remarks
Command B<ch><deg>
Set the backlash adjustment value.
Argument <deg>
Value
-99,999 ~ +99,999
Initial value +100
Reply Nothing
Example B0+400 Set backlash adjustment value of CH3 to 500.
Remarks Only remote mode. And the motor is stopped.
CW
Without backlash adjustment move
With backlash adjustment move
CCW
destination
desti
backlash adjustment value
destination
desti
backlash adjustment value
CW
CCW
Without backlash adjustment move
With backlash adjustment move and auto adjust
With backlash adjustment move and no auto adjust