8 Timing out signal output
56
8 Timing out signal output
From the four channels that are displays on the LCD, you can get output signal of TTL
level according to the current pulse position from LEMO connector on the front panel. Type
of signal is available pulse signal and GATE signal.
GATE signal
When the position is within the range of the end point from the start of the current point,
the output is H level. The output is similar even if a number of start and end points are
replaced.
When you have the same value of the start and end points, it will be output when the
signal of the width of the pulse output speed has passed that point.
(Example) Set START=10000, STOP=10000 and 1000PPS,
GATE signal having a pulse width of 1ms is output when it has passed
through the position 10000.
Pulse signal
When the motor direction is to the end point from the start point, the pulse signal (width:
200ns ~ 1ms) is outputted if it passes through START. And the pulse signal is outputted
every time the value of the interval only proceed until it passes through STOP from
START.
If the motor direction is reversed, the pulse signal doesn't generated.
When the motor direction is CCW, and if you want to output the pulse, please set the
value of the start point that is larger than the end point.
Timing out start point
Timing out end point
GATE output
Timing out start point
Timing out end point
Pulse output
GATE output
Motor direction
Pulse output
Motor direction
Timing out
Interval